GET /v1/factor-of-evaporation

Factor of evaporation and real capacity

Essayez-le en direct

10 appels gratuits par jour — sans inscription, sans clé API. Passe par la passerelle oanor.

En-têtes personnalisés (facultatif)
api.oanor.com/boiler-api

Ça marche. Récupérez une clé API et utilisez-la dans votre projet.

Obtenez une clé API

Extraits de code

curl "https://api.oanor.com/boiler-api/v1/factor-of-evaporation" \
  -H "x-oanor-key: oanor_test_..."
await fetch("https://api.oanor.com/boiler-api/v1/factor-of-evaporation", {
  headers: { "x-oanor-key": "oanor_test_..." }
});
$ch = curl_init("https://api.oanor.com/boiler-api/v1/factor-of-evaporation");
curl_setopt($ch, CURLOPT_HTTPHEADER, ["x-oanor-key: oanor_test_..."]);
curl_setopt($ch, CURLOPT_RETURNTRANSFER, true);
$out = curl_exec($ch);
import requests
requests.get(
    "https://api.oanor.com/boiler-api/v1/factor-of-evaporation",
    headers={"x-oanor-key": "oanor_test_..."}
)

Exemple de réponse

Une réponse réelle de ce endpoint, capturée lors du dernier contrôle de santé.

{
    "data": {
        "note": "The factor of evaporation = (total heat of the steam − the feedwater heat) ÷ 970.3. It is always ≥ 1 because real feedwater is below 212 °F, so the boiler must add the sensible heat too. Divide a 'from and at 212 °F' rating by this factor to get the real output at your feedwater temperature — which is why preheating feedwater (e.g. with an economiser) raises capacity and saves fuel.",
        "inputs": {
            "feedwater_temp_f": 60,
            "from_and_at_lb_hr": 1000,
            "steam_total_heat_btu_lb": 1150.4
        },
        "actual_output_lb_hr": 864.5,
        "factor_of_evaporation": 1.1568
    },
    "meta": {
        "timestamp": "2026-06-06T23:53:55.985Z",
        "request_id": "c8faedc3-813c-4ad6-a3af-97d58c8bf992"
    },
    "status": "ok",
    "message": "Factor of evaporation",
    "success": true
}